Double Float® Master

Mechanically-Activated, Wide-Angle Pump Switch

double float master

The Double Float® Master pump switch is designed to directly control pumps up to 15 FLA, 90 LRA, 120 VAC or 240 VAC in non-potable water, water and sewage applications.

The Double® Float Master pump switch consists of two mechanical floats and a splice tube. The splice tube contains a holding relay which enables the floats to function in series. The holding relay eliminates pump chatter in turbulent conditions allowing the Double Float® Master pump switch to operate relay control panels for larger pump applications.

This switch is well suited for confined space applications requiring an accurate pumping range. It is not sensitive to rotation or turbulence. This switch is voltage sensitive – use with correct voltage.

double float master

Features

  • Controls pumps up to 15 FLA, 90 LRA, 120 VAC or 240 VAC
  • Adjustable pumping range of 3 – 48 inches (7.6 – 122 cm) with increased pumping range up to 6 feet (1.8 meters) available
  • Includes standard mounting clamps and boxed packaging
  • Double Float® Master Pump Switch Diagrams

Options:
  • For pump up or pump down applications as specified by part number
  • With a 120 VAC or 240 VAC piggy-back plug
  • Without a plug for direct wiring (120 VAC units can be used only with 120 VAC applications within specified amp ratings. 240 VAC units can be used only with 240 VAC applications within specified amp ratings)
  • In standard cable lengths of 15, 20, or 30 feet (5, or 10 meters) – longer lengths available
UL Recognized, CSA Certified
Five Year Limited Warranty

Specifications

CABLE:
  • Attached to Float Housing:
    • Flexible 18 gauge, 2 conductor (UL, CSA) SJOW, water-resistant (CPE)
  • Above Splice:
    • Flexible 14 gauge, 3 conductor (UL, CSA) SJTW, water-resistant thermoplastic
FLOATS:
  • 2.74 inches diameter x 4.83 inches long (7.0 x 12.3 cm) high impact, corrosion resistance, PP housing for use in sewage and water up to 140°F (60°C)
ELECTRICAL:
  • 120 VAC 50/60 Hz Single Phase:
    • Maximum Pump Running Current (FLA): 15 amps
    • Maximum Pump Starting Current (LRA): 90 amps
  • 240 VAC 50/60 Hz Single Phase:
    • Maximum Pump Running Current (FLA): 15 amps
    • Maximum Pump Starting Current (LRA): 90 amps

NOTE: This switch must be used with pumps that provide integral thermal overload protection.

A Pump Switch is designed for Horsepower (HP) rated loads and is not suitable for control (pilot duty) applications. It will fail prematurely when switching loads less than 1 Amp at 120 VAC. Select a float switch from our Control Switch offering for control applications.

.

Looking for support
or purchase information?

Contact us