| Model 314 control panel | |||
| |||
| The Model 314 control panel is designed for applications requiring intrinsically safe float circuits or other circuit extensions. This panel controls one 208/240/480 VAC three phase pump. Two control switches activate a magnetic motor contactor to turn the pump on and off. If an alarm condition occurs, an additional alarm switch activates the audio/visual alarm system. Common applications include pump chambers, lift stations, or other installations classified as hazardous locations requiring intrinsically safe circuits. UL Listed relating to hazardous locations with intrinsically safe circuits.UL Listed. - Multi-tap control transformer 208/240/480 VAC primary provides 120 VAC control voltage - Motor protective switch for short circuit and overload protection - Intrinsically safe relays - IEC motor contactor - Pump run light - HOA switch - Terminal block - Control/alarm fuse - Control on/off switch - Three (on, off, alarm) control switches | |||
| |||