SJE-Rhombus
{rsMainGraphic.title}

SJE-Rhombus Engineered Controls - Controllers

  • Product Info
  • Features
  • Specs
  • Downloads

SP6R-LSC Controller

Duplex Microprocessor-Based Controller

The SP6R-LSC Duplex Lift Station Controller monitors level in wet wells.

The SP6R-LSC Duplex Lift Station Controller is simplicity at its best, incorporating numerous control and monitoring features into one user-friendly unit. 

The easy-to-use microprocessor-based controller monitors the level in the wet well via a submersible pressure transducer or any other device with a 4-20 mA signal output.  The controller provides pump alternation and has a simulation feature with automatic time out.  The SP6R-LSC displays:

  • Level Set Points
  • Pump Run Time
  • Pump Cycle Count
  • Actual Level

The SP6R-LSC Duplex Lift Station Controller is also available in a NEMA 4X enclosure.  These units are ideal for replacing float switch or bubbler control systems.  Complete, turn-key control systems are also available through our engineered products line.

 

SP6R-LSC Controller

Features:

  • 4-20 mA level input with configurable zero and span
  • Bar graph display of wet well level, configurable to feet, inches, percentage or metric
  • Six level set points:
    • High water alarm (with relay output)
    • Start lag pump (with relay output)
    • Start lead pump (with relay output)
    • Stop lag pump
    • Stop lead pump
    • Low level (with relay output)
  • Run time meter for each pump
  • Cycle counter for each pump
  • Automatic alternation
  • Simulation mode with automatic time out
  • Lag pump start delay (1-6000 sec.)
  • Pump run indication
  • Seal fail indication:
    • Indication only
    • Lock out pump with manual reset
    • Run pump as lag only
  • Pump over temperature indication (2 modes):
    • Lock out pump with auto rest
    • Lock out pump with manual rest
  • Analog input: 0.1% resolution 4-20 mA signal, built-in noise filtering and averaging
  • Eight character, alpha-numeric, avionics-grade LED for process value display and program parameters
  • 6 programmable relay outputs
  • On board 24 VDC, 30 mA excitation voltage
  • Easy navigation and set up with keypad
  • Simulation mode to verify proper relay sequence operation
  • Competitively priced


 

 

SP6R-LSC Controller

Specifications:

INPUT TYPE:
4-20 mA signal

INPUT IMPEDANCE:
100 ohms

INPUT RESOLUTION:
12 - bits, 0.1% of full scale

SAMPLING CYCLE TIME:
100 mS

AVERAGING:
8 consecutive samples

ACCURACY:
0.5% of full scale

EXCITATION VOLTAGE:
24 VDC, 30 mA available for loop powered transducers

RELAY OUTPUTS:
Four (4) programmable relay outputs with LED indication.  "Form C" (SPDT) contacts rated at 10 amps at 240 VAC.

LEVEL DISPLAY:
Eight (8) character, alpha-numeric LED for process value and program parameters.  The avionics-grade display is sharp and clear, even in direct sunlight from 10 feet away.

POWER:
24 VDC (+/- 10%), 200 mA nominal, 400 mA maximum

OPERATING TEMPERATURE
-15oC to 70oC (0oF to 150oF) at up to 0-90% RH non-condensing

ENCLOSURE RATING:
Front Panel: IEC Standard IP54 (with additional gasket) for indoor use
Rear Case: IEC Standard IP20

BAR GRAPH:
20 segment bar graph display for process value - each bar represents 5% of full scale.


 

Available Downloads

Adobe Acrobat is a free download to view .pdfs

Visit our downloads section of this website for additional literature.

USA  French Canadian  Chinese

French  German  Italian  Spanish